Categories
Article No. 296.044.052
E-Number 808 476 000
Technical specification
Construction size 2 modular spacing  
SPD type T2 / T3  
Number of poles 2  
max. discharge current (Imax) 40 kA  
Nominal line voltage Un AC 230 V  
Continuous voltage AC max. 275 V  
Nominal frequency [fn] 0 - 100 Hz  
Nominal discharge surge current (8/20) 20 kA  
Combined shock [Uoc] 10 kV  
Voltage protection level [Up] 1.1 kV  
Protection level max. (at 5kA) 0.8 kV  
Protection level max. (at 12.5kA) 0.95 kV  
Protection level max. (at Imax) 1.5 kV  
Operating current [Ic] 0 kA  
Follow current [IF] 0 kA  
follow current extinguishing capability [Ifi] Unendlich kA eff  
Response time [ta] ≤20 ns  
TOV-voltage L-N [UT] 450 V / 5 sec.  
Short circuit resistance (Icw) 25 kA  
Fault indication Mechanisch, Rot  
Temperature range -40 - 85 °C
Degree of protection IP20  
Fuse max. (gG) 125 A  
Mounting on Hutschiene 35 mm  
Technische Spezifikation
Material housing Thermoplast PEI UL-94-5VA  
Technical specification
Signaling on the device Optic  
Signaling contact Yes  
Connection cross section solid / stranded max. 1.5 mm²  
Switching capacity signaling contact 250 V / 0,5 A (AC) - 30 V / 2 A (DC)  
System configuration TN  
Category type 2 Yes  
Nominal cross section conductor 2.5 - 25 mm²
Voltage protection level L-N [Up] 1.1 kV  
Nominal discharge current [In] 20/Pol  
Short-circuit-proof Yes  
Integrated backup fuse No  
With remote signalling contact Yes  
Mounting method DIN rail (top hat rail) 35 mm  
Degree of protection (IP) IP20  
Standards
Homologation VDE, ÖVE und UL  
Test standards International IEC 61643-11  
Test standards USA UL 1449 ed.3  
Test standards Europe EN 61643-11  
Commercial specification
Customs number 85363000  
country of origin undefined  
Logistic specification