DAC1-13S DAC1-13S

Characteristics
- surge protector type 1+2
{- Ableitfähigkeit pro Pol: Iimp = 12.5kA (10/350µs)}
- 10 years warranty
{- Steckbares Schutzmodul}
{- Thermische Trennvorrichtung}
{- Optische Anzeige serienmässig}
- remote signaling
{- Erzeugt keinen Kurzschlussstrom}
SPD type
T1 / T2
Network configuration
Yes
System configuration
TN-S
Continuous voltage AC max.
275
Nominal line voltage Un AC
230
Nominal frequency [fn]
0.0 - 100.0 Hz
TOV-voltage L-N [UT]
335 V / 5 sec.
Operating current [Ic]
0
Follow current [IF]
0
follow current extinguishing capability [Ifi]
Unendlich kA eff
Nominal discharge surge current (8/20)
20
Discharge current max. (8/20) µs [Imax]
50
Impulse current [Iimp]_(10/350)
12.5
max. discharge current (Imax)
50
Voltage protection level max. (by In) [Up]
1.3 kV
Protection level max. (at Imax)
1.3
Response time [ta]
<20 ns
Exhausting
No
Short circuit resistance (Icw)
50
Integrated backup fuse
No
Fuse max. (gG)
315
Signaling on the device
Optic
Nominal cross section conductor
2.5 - 25.0 mm²
Remote signalling
Yes
Connection cross section solid / stranded max.
1.5
Switching capacity signaling contact
250 V/0,5 A (AC) / 30 V / 3 A (DC)
Fault indication
mechanisch, Rot
Mounting on
Hutschiene 35 mm
Material housing
Thermoplastik PEI UL-94-V0
Temperature range
-40.0 - 85.0 °C
Mounting method
DIN rail (top hat rail) 35 mm
Degree of protection
IP 20
Degree of protection (IP)
IP20
Test standards Germany
DIN EN 61643-11
Test standards Europe
DIN EN 61643-11
Test standards International
IEC 61643-11
Test standards USA
UL 1449 ed.4
Test standards France
DIN EN 61643-11
Homologation
KEMA / EAC