Categories

Surge protection 296.072.774

Type: B 280

Characteristics
Citel B 180 and B 280 surge protectors have been designed to protect your single and dual telephone and data lines against harmful lightning surges and electrical transients. The two-staged protection circuit consists of a combination of powerful gas-tube technology and fast switching diodes. These compact boxes are designed for wall mounting and screw connection.

Article No. 296.072.774
E-Number 970 523 003
Technical specification
Number of wires 4  
Continuous voltage DC max. 53 V  
Signal - maximum continuous voltage AC 37 V  
Operating voltage max. [UcDC] 53 V  
Applications with interface ADSL  
Nominal line voltage Un DC 48 V  
Continuous voltage AC max. 38 V  
Impulse current [Iimp]_(10/350) 2.5 kA  
Nominal discharge surge current (8/20) 5 kA  
Nominal load current 0.3 A  
Voltage protection level [Up] 0.07 kV  
Response time [ta] <1 ns  
Fault indication Kurzschluss  
Temperature range -40 - 80 °C
Dimensions Siehe Massbild  
Signaling on the device None  
Signal frequency 10 MHz
Discharge current max. [Imax] 20 kA  
Connector (information technology) Clamp  
Nominal cross section conductor 0.4 - 1.5 mm²
Nominal discharge current [In] 5  
Signal nominal load current 0.3 A  
Mounting method Other  
With remote signalling contact No  
Degree of protection (IP) IP20  
Standards
Test standards International IEC 61643-21  
Test standards USA UL497A  
Commercial specification
Customs number 85363000  
country of origin undefined  
Logistic specification
VPE Weight 0.184 kg