Characteristics
{- Kompakter Typ 3 Überspannungsschutz}
- 10 years warranty
- remote signaling
{- Steckbares Schutzmodul}
- remote signaling

System configuration
TN  
Continuous voltage AC max.
275 V  
Nominal line voltage Un AC
230 V  
TOV-voltage L-N [UT]
335 V / 5 sec.  
Follow current [IF]
0 kA  
follow current extinguishing capability [Ifi]
unendlich  
Discharge current max. (8/20) µs [Imax]
15 kA  
Protection level max. (at Imax)
0.9 kV  
Short circuit resistance (Icw)
10 kA  
Integrated backup fuse
No  
Fuse max. (gG)
125 A  
Signaling on the device
Optic  
Remote signalling
Yes  
Connection cross section solid / stranded max.
1.5 mm²  
Switching capacity signaling contact
250 V/0,5 A (AC) / 30 V / 3 A (DC)  
Fault indication
mechanisch, Rot  
Mounting on
Hutschiene 35 mm  
Mounting method
DIN rail (top hat rail) 35 mm  
Degree of protection
IP 20  
Degree of protection (IP)
IP20  
Test standards Germany
DIN EN 61643-11  
Test standards Europe
DIN EN 61643-11  
Test standards International
IEC 61643-11  
Test standards USA
UL 1449 ed.4  
Test standards France
DIN EN 61643-11  
Homologation
KEMA / EAC  
   
Article No. E-Number      SPD type Number of poles Response time [ta] Nominal cross section conductor VPE Quantity
   
291.610.221 new label T3 2 <20 1.5 - 10 1
291.610.222 new label T3 4 <20 1.5 - 10 1