DACF25S DACF25S

Characteristics
- 10 years warranty
- remote signaling
{- Integrierte Vorsicherung}
- 10 years warranty
{- Steckbares Schutzmodul}
- remote signaling
SPD type
T2
Continuous voltage AC max.
275
Nominal line voltage Un AC
230
Nominal frequency [fn]
0.0 - 100.0 Hz
TOV-voltage L-N [UT]
335 V / 5 sec.
Operating current [Ic]
0
Follow current [IF]
0
follow current extinguishing capability [Ifi]
Unendlich kA eff
Nominal discharge surge current (8/20)
15
Discharge current max. (8/20) µs [Imax]
25
max. discharge current (Imax)
25
Voltage protection level max. (by In) [Up]
1.25 kV
Protection level max. (at Imax)
1.25
Voltage protection level [Up]
1.25
Response time [ta]
<20 ns
Short circuit resistance (Icw)
100
Integrated backup fuse
Yes
Signaling on the device
Optic
Nominal cross section conductor
2.5 - 25.0 mm²
Remote signalling
Yes
Connection cross section solid / stranded max.
1.5
Switching capacity signaling contact
250 V/0,5 A (AC) / 30 V / 3 A (DC)
Fault indication
mechanisch, Rot
Mounting on
Hutschiene 35 mm
Material housing
Temperature range
-40.0 - 85.0 °C
Mounting method
DIN rail (top hat rail) 35 mm
Degree of protection
IP 20
Degree of protection (IP)
IP20
Test standards Germany
DIN EN 61643-11
Test standards Europe
DIN EN 61643-11
Test standards International
IEC 61643-11
Test standards USA
UL 1449 ed.4
Test standards France
DIN EN 61643-11
Homologation
KEMA / EAC